| Standard | IEC/EN61009-1 | | Protection | Ground fault, Overcurrent and short circuit | | Type of trip | Ground fault: Electronic | | Overload and short circuit: Thermo-magnetic | | No. of poles | 1P+N,1 Module, N line with disconnected | | Type | AC, A | | Rated current In | 6,10,16,20,25,32,40A | | Rated sensitivity currents I△n | 10,30,100,300mA | | Residual current off-time under I△n | ≤0.1s | | Reted residual making and breaking capacity (I△m) | 500A(In≤50A) | | Rated voltage Ue | 240V~ | | Rated frequency | 50/60Hz | | Rated breaking capacity | 3KA | | Energy limiting class | 3 | | Rated impulse withstand voltage (1.2/50) Uimp | 4,000V | | Dielectric test voltage at ind. Freq. for 1min | 2kV | | Thermal release characteristic | (1.13-1.45) x In | | Magnetic release characteristic | B:(3-5) x In, C:(5-10) x In | | Electrical life | 4,000 Cycles | | Mechanical life | 10,000 Cycles | | Contact position indicator | Yes | | Protection degree | IP20 | | Ambient temperature | -25℃~+40℃, Max.95% humidity | | Terminal connection type | Cable/Pin-type busbar | | Max. terminal size for cable | 16mm2 | | Max. tightening torque | 2.5N.m | | Installation | Mounting on 35mm DIN rail | | Connection | From top and bottom |
|
|