Collect
  • Parameter
StandardIEC/EN61008-1
ProtectionGround fault
Type of tripElectro-magnetic
Type of protection (electric leakage)AC,A,B,G,S
No. of poles2P (1P+N),4P(3P+N)
Rated current In6,10,16,20,25,32,40,50,63A
Rated sensitivity currents I△n10,30,100,300mA
Residual current off-time under I△n≤0.1s
Rated residual making and breaking capacity(I△m)500A(In≤40A),10In(In>40A)
Rated voltage Ue1P+N: 230/240V~,  3P+N:400/415V~
Rated frequency50/60Hz
Rated breaking capacity6KA
SCPD fuse6000,  10000
Rated impulse withstands voltage (1.5/50) Uimp4,000V
Dielectric test voltage at ind. Freq. for 1min2kV
Electrical life2,000 Cycles
Mechanical life4,000 Cycles
Contact position indicatorYes
Protection degreeIP20
Ambient temperature-25°C to +55°C, Max.95%humidity
Terminal connection typeCable/Pin-type busbar/Fork-type busbar/U-type busbar
Max. terminal size for cable50mm²
Max. tightening torque2.5N.m
InstallationMounting on 35mm DIN rail
ConnectionFrom top and bottom